The catalog¶
Everything you can put on a designer HMI, by catalog section. Pick the Type of a piece of equipment on the General tab of its settings; you can change it later without losing its tags.
Tags marked (command) send a value to the equipment and need a writable channel. Tags in italics are optional: leave them empty if the site doesn't have that signal.
One state code instead of separate tags
Pumps, blowers, mixers, aerators, chemical feed skids and screens take either separate Call, Running, Faulted and Hand / Off / Auto tags (the D6 apps send these), or one State code from controllers that report a single number per unit: 0 Off, 1 Auto ready, 2 Auto running, 3 Hand stopped, 4 Hand running, 5 Failed to start, 6 Fault, 7 Not available. Use one way or the other.
Equipment¶
| Equipment | Types | Tags |
|---|---|---|
| Pump | Centrifugal; Centrifugal (side discharge); Submersible; Submersible (well, inline); Peristaltic | Call (run output), Running, Faulted, Hand / Off / Auto, State code, Speed, Current, Seal fail |
| Valve | Gate, Butterfly, Ball, Check, Plug, 3-way | Opened feedback, Closed feedback, Open call (command), Close call (command) |
| Modulating valve | Butterfly, Ball | Position command (command), Position feedback |
| Tank | Vertical, Horizontal, Wet well, Standpipe, Pedesphere, Clearwell, Ground storage, Chemical day tank | Level; Start, Lag start, Stop and Low cutout level lines; Full level (tag) |
| Blower | Positive displacement, Centrifugal, Turbo | As a pump's run tags, plus Speed |
| Mixer | Top-entry, Submersible, Top-down (overlay) | As a pump's run tags |
| Aerator | Surface, Floating aspirator, Diffused-air grid | As a pump's run tags |
| Compressor | Air compressor, With receiver tank | Running, Fault, Loaded, Pressure |
| Motor / VFD | Motor, VFD | Running, Fault, Speed, Current |
| Pressure-reducing valve | Inlet pressure, Outlet pressure, Position | |
| Weir / flume | V-notch weir, Rectangular weir, Parshall flume | Head, Flow, Primary device (picks the picture from a SmartFlow's setting) |
| Clarifier | Circular, Rectangular | Drive running, Fault, Torque |
| Filter | Gravity (media), Pressure, Membrane | Filter state code, In service, Backwashing, Filtering to waste, Air scour, Level, Head loss (see Filters) |
| Aeration basin | Air on, Dissolved oxygen | |
| Digester | Fixed cover, Floating cover | Level, Temperature, Gas pressure |
| Lift station wet well | Duplex (2 pumps), Triplex (3 pumps), Quadplex (4 pumps) | Wet well level, High level float, Low level float, Pump 1 running, Pump 2–4 running, Pump 1–4 fault, level lines |
| Chemical feed skid | As a pump's run tags, plus Day tank level and Feed rate | |
| Chlorine gas system | Cylinder weight, Leak alarm | |
| Screen | Bar screen, Step screen, Drum screen | As a pump's run tags, plus Differential level |
| Generator | Running, Fault, Fuel level, Output | |
| Transfer switch | Utility available, Load on generator |
Mixers have no connection points, so pipes don't attach to them; the Top-down (overlay) type sits on top of a basin or tank drawn from above.
Instruments¶
| Instrument | Types | Tags |
|---|---|---|
| Flow meter | Magnetic, Ultrasonic (clamp-on), Turbine, Open channel | Flow, Total |
| Pressure transmitter | Transmitter, P&ID bubble | Pressure |
| Level sensor | Radar / ultrasonic, Pressure transducer, Float string | Level |
| Float switch | High, Low, High-high | Tripped |
| Analyzer | Chlorine, pH, Turbidity, Dissolved oxygen, ORP, Conductivity, Ammonia | Value, Alarm |
Indicators and controls¶
| Widget | What it does | Tags |
|---|---|---|
| Text box | A value with its units. Tick Operators can change the value (setpoint) to make it a setpoint | Value |
| Setpoint | A text box that operators can type a new value into | Value (command) |
| LED | A Lamp or a Status pill, lit when its tag is on | Value |
| Multi-switch | Buttons for each choice of a multiple-choice channel, such as Hand / Off / Auto | Tag (command) |
| Radial gauge | An arc gauge, with low and high alarm marks | Value |
| Linear gauge | A bar gauge | Value, Setpoint (a marker on the bar) |
| Trend graph | Up to six pens over the last hour, 6 hours or 24 hours (Time shown). Each pen can have its own line name | Pen 1, Pen 2–6 |
| Push button | Sends one pulse, such as Reset or Start | Command (pulse) (command), Lit when |
| Toggle | On / off switch | Tag (command) |
| State label | Text and colour for each value of a number. States is a list like 0=Stopped:off, 1=Running:run, 2=Fault:fault (colours: off, run, warn, fault, accent) |
Value |
| Valve indicator | OPEN, CLOSED or MOVING, plus the position with a bar | Opened, Closed, Position |
| Alarm list | The open alarms at the location (see Run mode) | none |
| Counter | A total, with a Period label such as Today | Value |
| Data table | Up to six values in rows | Row 1, Rows 2–6 |
| Comms badge | Whether a device is online, with its signal and battery | Online, Signal, Battery |
| Site power | Power and battery status of a site | Power loss, Bad battery, Solar voltage, Battery voltage |
| Settings button | Opens a list of commissioning settings, so they don't clutter the screen (see Run mode) | One per setting: connect one and an empty Add a setting appears for the next |
Navigation¶
| Widget | What it does |
|---|---|
| Map tile | A small map with an alarm light for up to three sites (Site 1–3 alarm) |
| Screen link | A button for opening another screen. Not working yet: in Run mode it only says which screen it would open |
Panels and app panels¶
Ready-made groups of equipment and readouts, already wired together. See Panels.
- Panels: Pump control, Valve control, Tank, Lift station overview, Well site, Blower, Chemical feed, Filter overview, Filters (common), Backwash.
- App panels, one per D6 app: SmartPump Duplex, SmartPump Triplex, SmartWell Single, SmartWell Multi master, SmartWell Multi well, Smart Lift, SmartMeter, SmartFlow, SmartLevel, Smart Tower, SmartLeak.
- My panels: panels saved by people in your account.
Draw¶
Pipe, Line, Rectangle, Ellipse, Text, Group box and Image. See Pipes and Drawing: shapes, text and pictures.