Skip to content

The catalog

Everything you can put on a designer HMI, by catalog section. Pick the Type of a piece of equipment on the General tab of its settings; you can change it later without losing its tags.

Tags marked (command) send a value to the equipment and need a writable channel. Tags in italics are optional: leave them empty if the site doesn't have that signal.

One state code instead of separate tags

Pumps, blowers, mixers, aerators, chemical feed skids and screens take either separate Call, Running, Faulted and Hand / Off / Auto tags (the D6 apps send these), or one State code from controllers that report a single number per unit: 0 Off, 1 Auto ready, 2 Auto running, 3 Hand stopped, 4 Hand running, 5 Failed to start, 6 Fault, 7 Not available. Use one way or the other.

Equipment

Equipment Types Tags
Pump Centrifugal; Centrifugal (side discharge); Submersible; Submersible (well, inline); Peristaltic Call (run output), Running, Faulted, Hand / Off / Auto, State code, Speed, Current, Seal fail
Valve Gate, Butterfly, Ball, Check, Plug, 3-way Opened feedback, Closed feedback, Open call (command), Close call (command)
Modulating valve Butterfly, Ball Position command (command), Position feedback
Tank Vertical, Horizontal, Wet well, Standpipe, Pedesphere, Clearwell, Ground storage, Chemical day tank Level; Start, Lag start, Stop and Low cutout level lines; Full level (tag)
Blower Positive displacement, Centrifugal, Turbo As a pump's run tags, plus Speed
Mixer Top-entry, Submersible, Top-down (overlay) As a pump's run tags
Aerator Surface, Floating aspirator, Diffused-air grid As a pump's run tags
Compressor Air compressor, With receiver tank Running, Fault, Loaded, Pressure
Motor / VFD Motor, VFD Running, Fault, Speed, Current
Pressure-reducing valve Inlet pressure, Outlet pressure, Position
Weir / flume V-notch weir, Rectangular weir, Parshall flume Head, Flow, Primary device (picks the picture from a SmartFlow's setting)
Clarifier Circular, Rectangular Drive running, Fault, Torque
Filter Gravity (media), Pressure, Membrane Filter state code, In service, Backwashing, Filtering to waste, Air scour, Level, Head loss (see Filters)
Aeration basin Air on, Dissolved oxygen
Digester Fixed cover, Floating cover Level, Temperature, Gas pressure
Lift station wet well Duplex (2 pumps), Triplex (3 pumps), Quadplex (4 pumps) Wet well level, High level float, Low level float, Pump 1 running, Pump 2–4 running, Pump 1–4 fault, level lines
Chemical feed skid As a pump's run tags, plus Day tank level and Feed rate
Chlorine gas system Cylinder weight, Leak alarm
Screen Bar screen, Step screen, Drum screen As a pump's run tags, plus Differential level
Generator Running, Fault, Fuel level, Output
Transfer switch Utility available, Load on generator

Mixers have no connection points, so pipes don't attach to them; the Top-down (overlay) type sits on top of a basin or tank drawn from above.

Instruments

Instrument Types Tags
Flow meter Magnetic, Ultrasonic (clamp-on), Turbine, Open channel Flow, Total
Pressure transmitter Transmitter, P&ID bubble Pressure
Level sensor Radar / ultrasonic, Pressure transducer, Float string Level
Float switch High, Low, High-high Tripped
Analyzer Chlorine, pH, Turbidity, Dissolved oxygen, ORP, Conductivity, Ammonia Value, Alarm

Indicators and controls

Widget What it does Tags
Text box A value with its units. Tick Operators can change the value (setpoint) to make it a setpoint Value
Setpoint A text box that operators can type a new value into Value (command)
LED A Lamp or a Status pill, lit when its tag is on Value
Multi-switch Buttons for each choice of a multiple-choice channel, such as Hand / Off / Auto Tag (command)
Radial gauge An arc gauge, with low and high alarm marks Value
Linear gauge A bar gauge Value, Setpoint (a marker on the bar)
Trend graph Up to six pens over the last hour, 6 hours or 24 hours (Time shown). Each pen can have its own line name Pen 1, Pen 2–6
Push button Sends one pulse, such as Reset or Start Command (pulse) (command), Lit when
Toggle On / off switch Tag (command)
State label Text and colour for each value of a number. States is a list like 0=Stopped:off, 1=Running:run, 2=Fault:fault (colours: off, run, warn, fault, accent) Value
Valve indicator OPEN, CLOSED or MOVING, plus the position with a bar Opened, Closed, Position
Alarm list The open alarms at the location (see Run mode) none
Counter A total, with a Period label such as Today Value
Data table Up to six values in rows Row 1, Rows 2–6
Comms badge Whether a device is online, with its signal and battery Online, Signal, Battery
Site power Power and battery status of a site Power loss, Bad battery, Solar voltage, Battery voltage
Settings button Opens a list of commissioning settings, so they don't clutter the screen (see Run mode) One per setting: connect one and an empty Add a setting appears for the next
Widget What it does
Map tile A small map with an alarm light for up to three sites (Site 1–3 alarm)
Screen link A button for opening another screen. Not working yet: in Run mode it only says which screen it would open

Panels and app panels

Ready-made groups of equipment and readouts, already wired together. See Panels.

  • Panels: Pump control, Valve control, Tank, Lift station overview, Well site, Blower, Chemical feed, Filter overview, Filters (common), Backwash.
  • App panels, one per D6 app: SmartPump Duplex, SmartPump Triplex, SmartWell Single, SmartWell Multi master, SmartWell Multi well, Smart Lift, SmartMeter, SmartFlow, SmartLevel, Smart Tower, SmartLeak.
  • My panels: panels saved by people in your account.

Draw

Pipe, Line, Rectangle, Ellipse, Text, Group box and Image. See Pipes and Drawing: shapes, text and pictures.