Expressions: combining tags

Any tag that only shows a value (not one that sends a command) can be an Expression instead of a single tag. Choose Expression… at the top of the tag list.

An expression on a header pipe

  1. Expression… in the tag list.
  2. The expression. Here the header flows when either filter is sending more than 10 gpm.
  3. Insert a tag… puts a channel's name in at the cursor, so you don't have to remember how it's spelled.
  4. The result, worked out as you type, or what's wrong with the expression (for example No channel called "filt3_flow" at this location).

Expressions work for on/off tags (a pipe's Flowing when, an LED, a pump's Running) and for values (a text box, a gauge, a flow meter's reading, a trend pen):

You want Expression
The header flows when both filters are sending water filter_1_flow > 10 AND filter_2_flow > 10
...when either one is filter_1_flow > 10 OR filter_2_flow > 10
A light that's on when any pump runs pump_1_running OR pump_2_running OR pump_3_running
A light that's on when the filter is offline NOT filter_1_in_service
The total flow of two meters filter_1_flow + filter_2_flow
A level in inches from a level in feet clearwell_level * 12
A scaled value tag1 + tag2 / (10 * tag3)
The larger of two pressures max(discharge_pressure, header_pressure)

Writing tags

Use the channel's name in lower case with spaces as _: Filter 1 Flow is filter_1_flow. If two devices have a channel with the same name, put the device first, filter_gallery.filter_1_flow; the error message tells you when you need to. [Device / Channel] in square brackets works for any name.

What you can use

Arithmetic + - * / % and ( )
Comparisons > < >= <= == (or =) != (or <>)
Logic AND OR NOT
Values numbers, true / false, on / off
Functions abs min max avg round(value, decimals) floor ceil sqrt if(test, then, else)

You can also write && for AND, two vertical bars for OR, and ! for NOT.

A tag on its own counts as on when it's above 0 and off at 0, so pump_1_running alone is the same as pump_1_running > 0. If a tag in the expression has no reading yet, the result shows ––.

Note

Expressions are worked out on the screen of whoever has the HMI open, so they're for what the HMI shows. They don't drive alerts, and a trend pen with an expression starts plotting when the HMI is opened. Commands and setpoints always need a single, writable channel.

Any or all of several tags

For simple cases there's also Several tags (any / all of them)…: pick the tags and whether any or all of them must be on.